Manual RF Shielded Doors: Single and Double Leaf
A shielded door is a moving part that has to hold an electrical joint across its whole perimeter, every time it closes, for twenty years, while people walk through it carrying things. The hinge, the frame and the seal are one problem, and if they were assembled separately they will drift apart.
Attenuation, by frequency
From our door data sheet. Note the shape of the curve: the low frequency magnetic end is where the door gives up, and the door leaf thickness decides it.
| Frequency | Standard leaf | Pneumatic leaf |
|---|---|---|
| 14 kHz | 60 dB | 75 dB |
| 50 kHz | 70 dB | 90 dB |
| 100 kHz | 80 dB | 100 dB |
| 1 MHz – 18 GHz | 100 dB | 100 dB |
Two different leaf specifications appear in our own catalogue, and the difference is not marketing. The 3 mm cold steel manual leaf gives 60 dB at 14 kHz. The pneumatic door leaf, built heavier because it is driven by a cylinder rather than a hand, gives 75 dB at 14 kHz and reaches 100 dB by 100 kHz. If your chamber is specified at 14 kHz 70 dB and you fit the manual door, the door is your limiting component and the test will show it.
Sizes
| Parameter | Standard | Maximum |
|---|---|---|
| Clear opening, single leaf | 1 000 × 2 000 mm | 1 500 × 2 100 mm |
| Frame, single leaf | 1 398 × 2 398 mm | 1 898 × 2 498 mm |
| Clear opening, double leaf | — | 2 100 × 2 100 mm |
| Threshold height | 150 mm | minimum 120 mm |
The threshold is the piece everyone wants removed and nobody can remove. 150 mm is a step to walk over every time. It exists because a door below it cannot carry a full depth double knife seal while staying under the floor load. Below 120 mm we will not build it, and anyone who says yes is trading seal depth for a ramp you will regret.
Above 1 500 mm clear width the leaf is too heavy for a single manual leaf and it becomes a double leaf, which means two leaves meeting in the middle, which means a third seal down the centre. That centre seal is the one that fails first in service, so if you are near that boundary, tell us early and we will look at whether a sliding or pneumatic door suits better.
What decides a door's life
The seal
Double knife, three layer beryllium copper finger strip, two knives on the leaf meshing with spring strips on the frame. We build this from a utility model patent, not as a copy of a European pattern.
The strips are mounted in U-shaped clips so a single strip comes out and goes back without disturbing its neighbours. In a room with four doors that matters: the maintenance is not a shutdown, it is an hour with a screwdriver.
The strips used on our field shelter doors passed a 30 000 cycle open and close fatigue test with no deformation or breakage. The strip profile is an arc so contact with the knife face is a line, which also means the closing action wipes dust off the contact rather than pressing it in. That is a dusty-site feature that turns out to matter in ordinary rooms too.
The frame and leaf travel together
Every door ships as one unit with its frame, assembled in the factory and transported assembled. This is the single most important thing we do and it is not normal practice. If the leaf is made in one shop and the frame in another, or the frame is welded on site and the leaf arrives later, the two will not be co-planar, the strip contact will be uneven, and the loss shows up in the 1 GHz range where you cannot compensate for it.
The knife
Carbon steel for wear resistance at the contact line, even though it is magnetic and other parts might not be. The knife sees rubbing contact thousands of times and hardness wins over permeability at that one component. On non-magnetic doors, such as MRI rooms, the choice changes entirely and the knife becomes brass.
The hinge
Line cut to hold the tolerance, 110 degree opening, with a limit stop that is mounted on an embedded plate. Without the stop, the leaf opens back onto the wall and the frame takes the load at one corner until the seal goes out of true.
Where the manual door wins
- No services required. No air line, no cable, no motor. On a site where compressed air is a contractor's problem, a manual door removes a whole interface.
- Nothing to break on the day. A cylinder fails with the door mid-travel and the room unsealed. A handle does not.
- One person, deliberately. A manual door closes at the speed someone turns the handle, not on a timer. For chambers where equipment is being positioned through the doorway, slowness is safer.
- Cheaper to buy and cheaper to maintain.
The trade is that a manual door opens slower, cannot be interlocked into an automated test sequence without adding a sensor, and needs a bigger clear space in front of the leaf for the swing and the handle.
Doors in context
A door is the largest penetration in a shielded room and its performance is the ceiling for the whole room. Our shielded room pages carry the room level figures; this page is only the door. If you are selecting a door for a room you are also buying, read both, because a 100 dB door in a room with eight vent windows does not give you a 100 dB room.
If the opening has to be large (a vehicle, a drive-in room), the door becomes a mechanism rather than an opening, and that is the pneumatic and sliding range.
Frequently asked
Can a manual door get an interlock?
Yes, a position switch on the frame, which is normally used for the test-in-progress lamp. Full safety interlocking is a site electrical matter and we will spec the switch, not the circuit.
Which way should the leaf open?
Whatever suits the room, the opening direction is a build option. Decide before the frame is made, because the leaf is handed.
Can we add a window to the door?
Yes, a shielded glass window to 80 to 300 mesh. It reduces the door's performance a little and makes the leaf heavier; add it at the design stage rather than as a retrofit.