HMEMC
中文站  |  sales.cn@hmemc.com  |  kubohua@hmemc.com  |  +86 519 8665 1804
English › Manual RF Shielded Doors

Manual RF Shielded Doors: Single and Double Leaf

A shielded door is a moving part that has to hold an electrical joint across its whole perimeter, every time it closes, for twenty years, while people walk through it carrying things. The hinge, the frame and the seal are one problem, and if they were assembled separately they will drift apart.

Attenuation, by frequency

From our door data sheet. Note the shape of the curve: the low frequency magnetic end is where the door gives up, and the door leaf thickness decides it.

FrequencyStandard leafPneumatic leaf
14 kHz60 dB75 dB
50 kHz70 dB90 dB
100 kHz80 dB100 dB
1 MHz – 18 GHz100 dB100 dB

Two different leaf specifications appear in our own catalogue, and the difference is not marketing. The 3 mm cold steel manual leaf gives 60 dB at 14 kHz. The pneumatic door leaf, built heavier because it is driven by a cylinder rather than a hand, gives 75 dB at 14 kHz and reaches 100 dB by 100 kHz. If your chamber is specified at 14 kHz 70 dB and you fit the manual door, the door is your limiting component and the test will show it.

Sizes

ParameterStandardMaximum
Clear opening, single leaf1 000 × 2 000 mm1 500 × 2 100 mm
Frame, single leaf1 398 × 2 398 mm1 898 × 2 498 mm
Clear opening, double leaf—2 100 × 2 100 mm
Threshold height150 mmminimum 120 mm

The threshold is the piece everyone wants removed and nobody can remove. 150 mm is a step to walk over every time. It exists because a door below it cannot carry a full depth double knife seal while staying under the floor load. Below 120 mm we will not build it, and anyone who says yes is trading seal depth for a ramp you will regret.

Above 1 500 mm clear width the leaf is too heavy for a single manual leaf and it becomes a double leaf, which means two leaves meeting in the middle, which means a third seal down the centre. That centre seal is the one that fails first in service, so if you are near that boundary, tell us early and we will look at whether a sliding or pneumatic door suits better.

What decides a door's life

The seal

Double knife, three layer beryllium copper finger strip, two knives on the leaf meshing with spring strips on the frame. We build this from a utility model patent, not as a copy of a European pattern.

The strips are mounted in U-shaped clips so a single strip comes out and goes back without disturbing its neighbours. In a room with four doors that matters: the maintenance is not a shutdown, it is an hour with a screwdriver.

The strips used on our field shelter doors passed a 30 000 cycle open and close fatigue test with no deformation or breakage. The strip profile is an arc so contact with the knife face is a line, which also means the closing action wipes dust off the contact rather than pressing it in. That is a dusty-site feature that turns out to matter in ordinary rooms too.

The frame and leaf travel together

Every door ships as one unit with its frame, assembled in the factory and transported assembled. This is the single most important thing we do and it is not normal practice. If the leaf is made in one shop and the frame in another, or the frame is welded on site and the leaf arrives later, the two will not be co-planar, the strip contact will be uneven, and the loss shows up in the 1 GHz range where you cannot compensate for it.

The knife

Carbon steel for wear resistance at the contact line, even though it is magnetic and other parts might not be. The knife sees rubbing contact thousands of times and hardness wins over permeability at that one component. On non-magnetic doors, such as MRI rooms, the choice changes entirely and the knife becomes brass.

The hinge

Line cut to hold the tolerance, 110 degree opening, with a limit stop that is mounted on an embedded plate. Without the stop, the leaf opens back onto the wall and the frame takes the load at one corner until the seal goes out of true.

Where the manual door wins

The trade is that a manual door opens slower, cannot be interlocked into an automated test sequence without adding a sensor, and needs a bigger clear space in front of the leaf for the swing and the handle.

Doors in context

A door is the largest penetration in a shielded room and its performance is the ceiling for the whole room. Our shielded room pages carry the room level figures; this page is only the door. If you are selecting a door for a room you are also buying, read both, because a 100 dB door in a room with eight vent windows does not give you a 100 dB room.

If the opening has to be large (a vehicle, a drive-in room), the door becomes a mechanism rather than an opening, and that is the pneumatic and sliding range.

What we would tell you not to do. Do not fit a manual door to a chamber specified at 14 kHz 70 dB and expect the room to hit it; the standard manual leaf is 60 dB there and the pneumatic leaf is 75 dB, so choose the door against the low frequency target, not the high frequency one. Do not remove the threshold to make the floor flat, because the seal depth is what it is. And if the door will be cycled more than about a hundred times a day, fit an automatic one; a manual door used like a bus station gate will need strip replacement on a schedule you will not enjoy.

Frequently asked

Can a manual door get an interlock?

Yes, a position switch on the frame, which is normally used for the test-in-progress lamp. Full safety interlocking is a site electrical matter and we will spec the switch, not the circuit.

Which way should the leaf open?

Whatever suits the room, the opening direction is a build option. Decide before the frame is made, because the leaf is handed.

Can we add a window to the door?

Yes, a shielded glass window to 80 to 300 mesh. It reduces the door's performance a little and makes the leaf heavier; add it at the design stage rather than as a retrofit.

Where we have shipped

Market notes and project references, by country:

GermanyPolandUnited StatesCanadaUAE & GulfIndiaVietnamIndonesiaTurkeySouth Africa

Ask about RF shielded doors

Five fields, no registration. We reply to every enquiry within one working day.

Or email sales.cn@hmemc.com