RF Shielded Rooms: Modular and Welded, 14 kHz to 18 GHz
A shielded room either attenuates or it does not, and the answer is decided at the penetrations. Panels are a solved problem. Doors, filters, vents, cable trays and the way the floor meets the wall are where rooms quietly lose 20 to 40 dB.
Two ways to build it
| Modular, bolted panels | Welded | |
|---|---|---|
| Panel | 3 m × 1 m double-sided hot dip galvanised steel, ≥ 2 mm, zinc ≥ 20 µm (≥ 275 g/m²), folded twice on all four edges | Steel sheet, continuously seam-welded |
| Joint | M10 flange bolts at 100 mm pitch through conductive mesh gasket | Continuous weld, no gasket to age |
| Assembly | On site, inside an existing building, no hot work | Welding on site, and that is the critical path |
| Typical performance | 80–100 dB depending on frequency | Higher, especially at 14 kHz |
| Can be moved | yes, panels re-used | no |
| Best for | upper floors, rented buildings, rooms that get reconfigured, sites with no hot work permit | metrology rooms, MRI rooms, military labs, low frequency work |
| Lead time | shorter, panels pre-fabricated in the factory | longer, site welding dominates |
Shielding effectiveness targets
Modular rooms are tested to EN 50147-1, GB/T 12190-2006, GJB 5792 and IEEE Std 299 methodology. Field, frequency, typical attenuation:
| Field | Frequency | Typical SE, modular room |
|---|---|---|
| Magnetic | 14 kHz | 60–75 dB |
| Magnetic | 100 kHz | 90–100 dB |
| Electric | 1 MHz – 1 GHz | 100 dB |
| Plane wave / microwave | 1 GHz – 18 GHz | 100 dB |
14 kHz is the hard one, and it is magnetic rather than electric. Thin galvanised steel is transparent to low frequency magnetic fields unless the panels are thick, the seams are continuous and every hole is closed. If your requirement is 14 kHz at 90 dB, welded construction with a high-permeability inner layer is a different product, not an option on the modular one.
A real specification, line by line
This is the reference design we issued in March 2022 for a shielded computer room, model HM-SR-16. It is a good example of how the numbers look before anyone starts talking about performance.
| Item | Model | Specification |
|---|---|---|
| Shield body | HM-SR-16 | Double-sided powder coated, 2 mm single layer galvanised steel, bolted modular structure, self-supporting steel frame with independent top support. Overall 11.5 m L × 2.70 m W × 2.80 m H. |
| Door | HM-SD-M | Manual swing shielded door, painted finish, clear opening 1.00 m × 2.00 m |
| Raised floor | — | Anti-static raised floor, 500 kg/m² load |
| Power filters | HM-PF-4×32A / HM-PF-2×32A | three phase 32 A 380 V 50/60 Hz ×1; single phase 32 A 220 V 50/60 Hz ×1 |
| Network | — | fibre optic conversion for the RJ45 port, 1000 Mbit/s |
| Vent windows | — | 300 × 300 mm, cut-off frequency 18 GHz, 8 units |
| Lighting | — | 8 × LED interference-free luminaires, clean PVC panel ceiling |
| Distribution | — | matching distribution board, breakers and light switches by the customer |
The shielding figure for that room
| Field | Frequency | Committed SE |
|---|---|---|
| Magnetic | 14 kHz | ≥ 60 dB |
| Magnetic | 100 kHz | ≥ 70 dB |
| Magnetic | 100 kHz – 100 MHz | ≥ 100 dB |
| Plane wave | 200 MHz | ≥ 100 dB |
| Plane wave | 500 MHz | ≥ 90 dB |
| Plane wave | 1 GHz | ≥ 90 dB |
| Microwave | 18 GHz | ≥ 80 dB |
Note what happens here. The room reaches 100 dB in the middle of the band and is committed to 80 dB at 18 GHz. That is not a weak room, it is a room with a normal door and eight vent windows in it, and the figures are honest about where the performance falls off. A vendor quoting a flat "100 dB, 14 kHz to 18 GHz" for a room with this many penetrations is quoting the panel, not the room.
What goes through the wall
Every one of these is a hole in the shield. The room's real performance is the shell figure minus the worst penetration.
| Penetration | Range we build | What matters |
|---|---|---|
| Shielded doors | manual, electric, pneumatic, sliding; 1.0, 1.2 and 1.5 m clear width; double-knife seals with beryllium copper finger strip | The door is the single biggest contributor to loss. Doors are assembled with their frame in the factory and shipped as one unit, so the frame cannot distort in transit — that is what destroys performance. |
| Power filters | 3 A to 2200 A; single and three phase; 220, 380, 400, 440 V; 400 Hz and DC variants | One filter per circuit, sized to the load. Adding a circuit later means cutting a hole, so plan spare capacity now. |
| Signal filters | telephone, LAN, USB, RS485, fire alarm, video, audio, fibre optic | Fibre is the cleanest option where the signal will allow it: no conductor, no waveguide cut-off to worry about. |
| Honeycomb vents | 2.5 to 8 mm cell, 5 to 120 mm thick, brazed, 10 kHz to 18 GHz | Cut-off frequency is set by cell size and depth. 300 × 300 mm at 18 GHz has become our standard vent. |
| Waveguide penetrations | fibre optic, infrared emitters, gas and water lines | Round waveguide, typically 50 mm |
| Shielded glass | 80 to 300 mesh, to GJB 151B | Mesh density sets the upper frequency limit |
| Filter wall / pass-through panel | 300 × 600 mm plates with N, BNC, SMA, FSMA, six-hole fibre waveguide, fibre interfaces | Removable with sealing compound, so a future upgrade does not mean cutting the shield. |
| Ground interface panel | 300 × 300 mm plates near the test table | N, SMA and FSMA connectors, quantity agreed per project |
How the vents are actually arranged
Vent windows are pre-mounted in the factory, with no bolt passing through the shield, because a bolt through the shield is a permanent leak and a permanent argument with the test house. Air comes in through wall mounted vents and leaves through the ceiling, above the light fittings. At about 4 m/s air speed that gives three to four air changes per hour. The vent units come apart for cleaning, and the external flange is insulated from the HVAC duct.
Grounding
Every power filter and the shield body itself go to a single point earth through a copper bar welded and bolted to the shield. Insulating pads under the panels hold the whole room above earth, so the resistance at the single point stays below 1.0 Ω. The copper tape from the building earth to that point should be at least 50 mm × 5 mm. The earth point itself is supplied by the customer, and the resistance has to be right before we connect.
The test that separates suppliers
Ask for shielding effectiveness measured on the finished room with the door closed, the filters fitted and the vents installed. Not the panel test, not a sample of panel, the room. A supplier who reports 100 dB at 1 GHz for a room with a 1.2 m door and six filter penetrations should be asked where exactly that measurement was taken.
In our experience the real number for a well-built modular room in the 1–18 GHz band is 80–100 dB, and the door seal decides which end of that range you get.
Reference projects
Germany, 2022
Three modular shielded chambers plus four RF doors, filters, vents and accessories for an automotive electronics test facility. Sizes 7 500 × 5 500 × 2 550 mm (two rooms) and 6 500 × 5 000 × 2 550 mm. Panels shipped: 51, 51 and 92. Two containers, heaviest pallet 2 100 kg.
Northwest Institute of Nuclear Technology, China
Eight double-layer, fully welded, moisture-proof shielded enclosures, model HM-SC-2507A, tested to GJB 5792A-2021 over 14 kHz to 10 GHz by the Jiangsu Institute of Metrology, reports E2025-40841 through E2025-40848.
China Academy of Engineering Physics, Mianyang
Production batch of shielded cabinets and small shielded rooms.
Frequently asked
Modular or welded, which should I choose?
If the building will not take hot work, if the room must later be moved or extended, or if you rent the floor, modular. If it is a metrology room, an MRI room, or a military laboratory where 14 kHz matters, welded. The price difference is smaller than the performance difference at the low end.
Can a modular room reach 100 dB at 1 GHz?
Yes, with good doors and correctly treated penetrations. Where it fails is usually the door seal and the cable tray, not the panels.
How much floor loading do the panels impose?
About 20–25 kg/m² of wall area for double-sided 2 mm galvanised panel with accessories. A 7.5 × 5.5 m room with 2.55 m walls is roughly two tonnes of steel. The structural check usually comes out fine, but it has to be done.
Do you provide the room in a building that is still under construction?
Yes, and that is the best time. Coordinating the floor slab, the door opening and the penetrations before the concrete is poured saves more money than any discount on the room itself.
What has to be ready before you arrive on site?
Floor loading around 2 000 kg/m², flatness within ±3 mm over any 3 m, damp-proofing and an insulating layer, insulation resistance above 2 MΩ, and a single point earth measured below 1.0 Ω. Ambient 10–40 °C and 10–95 % RH in both the control room and the test room. Seismic design to intensity 7.